Battery cable selection
Dale Scroggins wrote:
"Philippe" wrote in message
news:1770438.ul5SB0L1ai@GastonCoute...
wrote:
I am putting two 12V batteries together
http://www.batterymart.com/p-hawker-...t-battery.html
to make a 24V battery.
What size cable should I use to make the serial connection?
Longer the cable, bigger the cable...
connect two batteries with a 1"cable: a 6AWG cable will work
flat copper bar will be better (less losses):
http://www.aircraftspruce.com/catalo...ges/busbar.php
by
--
Volem rien foutre al païs!
Philippe Vessaire Ò¿Ó¬
** Posted from
http://www.teranews.com
**
A copper bar would indeed work much better than a short cable. If you
plan to join two standard aircraft batteries sharing the same battery
box, a well-fitted copper bar is easier to install than a cable.
You can make a bar by flattening a short section of 1/2" thick-wall
copper tubing (as used for refrigeration lines) in a vise and drilling
two 5/16" holes the correct distance apart (about two inches I think,
but you should measure). Coat it with grease each time it's installed
or it will corrode rapidly.
Beech Barons use a similar copper bar, tin-plated as I recall. You
could buy one.
The truly energetic could tin the bar with solder or, wait for it, tin.
Dan, U.S. Air Force, retired